General Specifications
Inputs
1 input, configurable for J, K , R or S thermocouples; Pt100; Ni100; Pt500; Pt1000; PTC; NTC; 0/4 to 20mA; 0 to 10VDC; potentiometers <= 6kΩ or <= 150kΩ
Outputs
Control relay 8 A; Alarm relay 5 A; SSR Control/Alarm; Open/Close logic (time-proportioned), RS485 Modbus RTU Slave (-ADT models)
Control Action
ON/OFF; PID Autotuning; Heating/Cooling PID
Configuration
Via push-button controls, or memory card, or LABSOFTVIEW software. Parameters protected by password
Display
3-digit red LED plus decimal point; green status LEDs
Accuracy
0.5% ± 1 digit for TC/RTD; 0.2% ± 1 digit for mA/V
Sampling Time
66 ms (selectable software filter on input and display)
Supply Voltage
230 V AC, 115 V AC, or 12-24 V AC/DC (depending on model)
Power consumption
2 W
Operating Temperature
0°C to 40°C
Operating Humidity
35% to 95% RH
Sealing
IP54 front panel (IP65 with gasket), IP30 housing, IP20 terminal blocks
Dimensions
32H x 74W x 58D mm
Product Markings
CE, UL, RoHS Compliant