General Specifications
Inputs
4 x analogue inputs, selectable 0-20 mA, 4-20 mA, 0-5 V, 0-10 V or digital ON/OFF
Optional plug-in board with 5 x digital or pulse inputs - contact Calex.
Optional plug-in board with 5 x digital or pulse inputs - contact Calex.
Compatible with
PyroCouple, PyroMini, PyroUSB, or any other sensor with analogue voltage or current output
Input resolution
10 bit (1024 increments) over 10 volts
Accuracy
0.25%
Sample rate
Configurable depending on data subscription (typically 1 transmission per 10 minutes, or 1 transmission per hour)
Outputs
-R models: 2 relay outputs rated 30 V DC, 2 A
Display
40 x 40 mm, 128 x 128 pixel resolution, backlit
Programming interface
USB port for configuration and firmware updates
Firmware updates
Via USB or GSM network
Warranty
2 years
Telecommunications Specifications
Approvals & Conformity
Conforms with R&TTE Directive; GE, GCF, FCC, PTCRB, IC, ANATEL approved
Modem type
Quad-band GSM & GPRS 850/900/1800/1900 Mhz
Output power
Class 4 (2 W) 850/900 MHzClass 1 (1 W) 1800/1900 MHz
Antenna
Internal antenna built in as standard. Optional external antenna via SMA connector
Environmental Specifications
Environmental rating
IP67
Dimensions
138 x 76 x 68 mm (exclusing cable glands)
Electrical Specifications
Input connector
Removable screw terminals, pitch 3.81 mm. 4 x 3-pin connectors for sensors, 1 x 2-pin connector for power
Power supply
3.9 V battery (-B models) or 6-24 V DC, 0.5 A (-DC models)
Output power to sensors
3.9 V (unregulated), 5 V or 21.6 V
Output current to sensors
31.25 mA max.